Installation
Provides the complete installation procedures and connection examples required for the device.
Product Fixation
Secure the product tightly with a fixing screw at the location to be mounted.

Power supply connection
-
Use the IEC/EN 62368-1 approved power adapter that supports higher power consumption than the product. If you wish to connect and use another device to the power supply adapter, you should use an adapter with a current capacity which is the same or larger than the total power consumption required for the terminal and another device.
- Refer to the Power in the product specifications for maximum current consumption specifications.
- Use a separate power supply for Secure I/O 2, the electric lock, and the product respectively. If connecting and using the power supply to these devices together, the devices may malfunction.
- DO NOT extend the length of power cable when using the power adapter.
Power-specific reader and lock power specifications
| Power | Reader (maximum current, number of devices) | Lock (maximum current, number of devices) |
|---|---|---|
| DC 12V | 600mA (300mA x 2) | 1.2A (600mA x 2) |
| DC 24V | 300mA (150mA x 2) | 600mA (300mA x 2) |
Maximum extension length by cable specification
The distance that can be connected may vary depending on the cable specifications and installation environment used for power connection. If cable connections are made improperly it may cause the device to malfunction. This product supports both DC 12V and DC 24V power supplies, so check the maximum extension length according to each cable specification and connect the power correctly.
| Cable Specification | DC 12V | DC 24V | ||
|---|---|---|---|---|
| Reader (300mA) | Lock (600mA) | Reader (150mA) | Lock (300mA) | |
| 14 AWG | 380 m | 190 m | 1540 m | 770 m |
| 16 AWG | 240 m | 120 m | 960 m | 480 m |
| 18 AWG | 150 m | 75 m | 600 m | 300 m |
RS-485 Connection
This product supports 3 RS-485 ports, and by daisy-chaining multiple Door Interfaces to the master device, you can configure up to 34 doors.
-
The maximum number of slave devices that can be connected to the product's RS-485 port is 4.
-
Up to 2 devices can be connected per port for RS-485 0 and RS-485 1.
-
If more than 3 devices are connected to a single RS-485 port, the desired device may not appear in the connectable list when searching for slave devices.
-
Use AWG26 or larger for RS-485 cables, and all wiring must comply with ANSI/NFPA 70 standards.
-
Use an AWG24 twisted pair with a maximum length of 1.2 km for the RS-485 cable.
-
It is recommended to use RS-485 cables with a characteristic impedance of 120 Ω.
-
Connect termination resistors (120 Ω) at both ends of the RS-485 daisy chain connection. If connected to the middle line, the signal level becomes smaller and the communication performance will deteriorate. Make sure to connect it to both ends of the daisy chain connection. Set this product's termination resistor switch to ON.
Relay Connection
Fail Safe Lock
In order to use the Fail Safe Lock, connect the NC relay as shown in the figure below. There is normally a current flowing through the relay for the Fail Safe Lock. When the relay is activated, blocking the current flow, the door will open. If the power supply to the product is cut off due to a power failure or an external factor, the door will open.
Fail Secure Lock
In order to use the Fail Secure Lock, connect NO relay as shown in the figure below. There is normally no current flowing through the relay for the Fail Secure Lock. When the current flow is activated by the relay, the door will open. If the power supply to the product is cut off due to a power failure or an external factor, the door will lock.